0.6/1 kV XLPE Insulated, Round Steel Wire Armoured, Multi-Core Cables With Copper Conductor
YXZ2V-U, YXZ2V-R, CU/XLPE/SWA/PVC, N2XRY
U, Solid conductor
R, Stranded conductor
Standards
TS IEC 60502, BS 5467
Technical Data
Max. operating temperature: 90°C
Max. short circuit temperature: 250°C (max. 5 sn.)
Rated voltage: 0.6/1 kV
Min. bending radius: 15 x D
D: Cable outer diameter
Application
These cables have a low dielectric loss, used in indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage.
Construction
1. Solid or stranded copper conductor.
2. XLPE insulation.
3. Filler.
4. Galvanized round steel wires.
5. Polyester tape.
6. PVC outer sheath.